Rockwell Automation FactoryTalk Service Platform
Discription

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk Service Platform Vulnerability: Improper Verification of Cryptographic Signature 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to retrieve user information and modify settings without any authentication. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Smart Security Manager, a software management platform, are affected: FactoryTalk Service Platform: Versions prior to v6.4 3.2 Vulnerability Overview 3.2.1 IMPROPER VERIFICATION OF CRYPTOGRAPHIC SIGNATURE CWE-347 A vulnerability exists in the affected product that allows a malicious user to obtain the service token and use it for authentication on another FTSP directory. This is due to the lack of digital signing between the FTSP service token and directory. If exploited, a malicious user could potentially retrieve user information and modify settings without any authentication. CVE-2024-21917 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: United States 3.4 RESEARCHER Rockwell Automation reported this vulnerability to CISA. 4. MITIGATIONS Rockwell recommends the…Read More

Back to Main